What it does -
The CC-97 and CC-95 controllers are fully automatic systems which will greatly reduce the amount of water used in continuous
flow rinse tanks. At the same time, they automatically maintain water quality, ensuring effective rinsing in water up to 180°F (82°C).
How it works -
The three parts of the system are easily installed. Submersible conductivity sensor is adjusted to either of the two microsiemen
scales and immersed in rinse tank. Controller set-point is then selected. Generally, rinse water contamination is caused by chemicals being "dragged in" and salts that are dissolved from the parts being rinsed. These solutions ionize and can be measured and controlled by their electrical conductivity. Rinse water cannot flow into the tank until the contamination level rises above the set-point. Sensor then signals for solenoid valve to open and add fresh water. When the dilution lowers the contamination to below the set-point, the solenoid valve will close. Indicator lights on controller signal operating power and valve position.

Application:
Ideal for plating rinse water
Performance: Conductivity
Features:
- Corrosion resistant Wall mount NEMA 12 enclosure w/ LED lamps: POWER ON, VALVE OPEN
- Submersion sensor - dual range0 to 500 micromhos and 500 to 5,000 micromhos w/ Variable set-point
- Solenoid valve Nylon (glass reinforced), 1" NPT 24 volt for safety
Benefits:
- Conserve rinse water - up to 85%
- Eliminate rejects from spotty rinsing
- Reduce waste treatment load
- Reduce sewer use charges
Product Bulletin
Operation and Service Guide